Current Blogs

Venturi Air Valve

Venturi valve is a kind of air volume regulation and control equipment based on the Venturi effect. It is a pressure independent, high regulation ratio, fast response, high precision air volume control valve, which is widely used in all kinds of risk environment.

EB Air Control Inc. Venturi Valves utilize fast-acting electric actuators that provide a fast response (<1 second) to ensures the airflow is maintained which is critical in areas requiring a specific threshold of air flow in order to protect individuals from airborne chemicals or particulates.

EB Air Control Inc.Venturi valve series products have been successfully used in chemical laboratories, biosafety laboratories, physical and chemical laboratories, animal laboratories, GMP pharmaceutical factories, hospital isolation wards and other fields.

FEATURES

  • All valves include a pressure independent assembly, factory-calibrated position controller.
  • The valve can be used as a standalone device or in a fully integrated system.
  • Valve controllers provide room pressurization, humidity, temperature, occupancy and emergency control.
  • Precise flow control – the factory calibrated flow rate controller are executed precisely throughout its operating range.
  • Self-balancing pressure independent operation – the valve maintains airflow set point by automatically compensating for static pressure fluctuations in the system.

ISO

EB AIR CONTROL INC. is registered to ISO 9001.

EB Air Control Inc. was incorporated to providing highest quality solutions, designs, develops, manufactures and markets products, systems and services to control the environment and airflow in critical spaces.

Warranty

EB Air Control Inc. guarantees all Venturi valves against defects in material and workmanship for a period of 2 years.

SPECIFICATIONS
Construction

  • Valve Body: 16-gauge aluminum or 304SUS or 316SUS valve body by continuous welded seam.
  • Available as uncoated or with corrosion resistant baked phenolic coating or composite Teflon coating.
  • Valve shaft: SUS 316 with composite Teflon coating
  • Valve cone and assemblies: 16-gauge aluminum and Celanex 3300, or with Phenolic/Teflon coating
  • Spring grade SUS304 spring and SUS 316 slider assembly with polyester or PPS.
  • Insulation: Concealed Polyethylene (PE) layer

Operating Range

  • Working Temp: 32°F~122°F (0°C~50°C) ambient
  • Storage/Transport: 14°F~140°F (-10°C~60°C) ambient
  • Working Humidity: 10%-90% non-condensing RH

Performance

  • Pressure independent range: 0.6”-3.0” WC (150Pa-750Pa)
  • Volume control accurate: ± 5%
  • No minimum entrance or exit straight duct runs required
  • Available in airflow control range: 60 ~ 17,000 m3/h
  • Response time: to change in command signal: <1 second to change in duct static pressure: <1 second
  • High adjustment ratio: up to 20: 1
  • Each valve is factory-calibrated at 51 airflow set points across the full operating range.
  • Valves available in diameter: 8 inch, 10 inch, 12 inch, and 14 inch
  • Valves can be ganged together to increase flow.
  • The product is delivered in full accordance with the site wiring requirements, using the plug-out mode, exempt from site wiring and debugging work.

Power

  • Operating Voltage: 110 ~ 230Vac 50/60Hz
  • Operating Current: <1A
  • Rated Power: 60W

Valve PLC Controller I/O

  • 1 way of sash sensor input
  • 4 way of digital input (active)
  • 4 way of relay output
  • 1 way of 0-10V output
  • 3 way of RS485 communication interface

Control Function

  • DI multi-mode air volume control
  • AI 0-10V voltage control
  • MODBUS RTU communication control
  • Fume hood face velocity control
  • Fume hood three-state air volume control
  • Intelligent lab control
  • Compensating fume hood duel-valve variable air volumecontrol

Regulatory Compliance

  • CE
  • FCC
  • This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
    1. This device may not cause harmful interference.
    2. This device must accept any interference received,
    including interference that may cause undesired operation.


Variable Air Volume Venturi Valev 51-set-point Calibration

DIMENSIONS

 

 

 

 

 

 

ebair_wpVenturi Air Valve

We are available to assist with any Air Movement Solutions.
For Partnership or Representation, send us an email.